Mecer 2000VA On-Line Tower UPS

R4,965 Incl. Vat

Out of stock
Please contact us via our chat window or an email, and we will try our best to find a solution for you.

SKU: 05C-UPS-08 Category: Tags: , ,

Product Detail

Product code: ME-2000-WPTU

Overview

Mecer 2000VA On-Line Tower UPS (ME-2000-WPTU) has a wide input voltage range and an available converter mode.

Features

This UPS can charge up to 90% in battery capacity within a 4 hour period. This UPS is generator compatible and the Waveform is Pure Sinewave.

Note

A UPS is not designed to provide continuous power, it allows a computer or device to keep running for a short period of time when the primary power source is lost.

Specifications

Phase: Single phase with ground
Capacity: 2000 VA / 1600 W

Input
Voltage Range
Low Line Transfer: 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5% (Ambient Temp. < 35°C) (based on load percentage 100% – 80% / 80% – 70% / 70-60 % / 60% – 0)
Low Line Comeback: 175 VAC / 155 VAC / 135 VAC / 125 VAC ± 5% (Ambient Temp. <35°C) (based on load percentage 100% – 80% / 80% – 70% / 70 – 60% / 60% – 0)
High Line Transfer: 300 VAC ± 5%
High Line Comeback: 290 VAC ± 5%
Frequency Range: 40HZ ~ 70 HZ
Power Factor: ≥ 0.99 @ nominal voltage

Output
Output Voltage: 200/208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode): ± 1%
Frequency Range (Synchronised Range): 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode): 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio: 3:1
Harmonic Distortion: ≤ 3 % THD (Linear Load), ≤ 6 % THD (non-linear load)

Transfer Time
AC Mode to Batt. Mode: Zero
Inverter to Bypass: 4 ms (Typical)
Waveform (Batt. Mode): Pure Sinewave

Efficiency
AC Mode: 89%
Battery Mode: 87%

Battery
Battery Type: 12 V 9 Ah
Numbers: 4
Typical Recharge Time: 4 hours to recover to 90% capacity
Charging Current (max.): 1.0 A
Charging Voltage: 54.7 VDC ± 1%

Indicators
LCD Panel: UPS status, Load level, Battery level, Input/output Voltage, Discharge timer and Fault Conditions

Alarm:
Battery Mode: Sounding every 4 seconds

Low Battery: Sounding every second
Overload: Sounding twice every second
Fault: Continuously sounding

Physical
Dimension, D x W x H (mm): 397  x 145 x 220
Net Weight (kgs): 17

Environment
Humidity: 20-90 % RH @ 0-40°C (non-condensing)
Noise Level: Less than 50dB @ 1 Meter

Management
Smart RS-232/USB: Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and Mac
Optional SNMP: Power management from SNMP manager and web browser